Exact Extract — Huawei HCSA-Presales-Data Center Facility (Modular DC) V1.0 Training Material, PDF page 53
“Detailed introduction of 4 basic configurations Power type 220/230/240V, 50/60Hz, 1Ph+N+PE 208V-2Ph+PE-60Hz Basic BC1L BC2L BC3L BC4L(Latin America) configuration Aisle type NO Cold and hot aisle containment UPS(KVA) 6 10 6 6 Cooling NO Integrated cooling Power input Single Single rPDU 1、2 (optional) 1、2 (optional) 2*40A/1P+2*40A/2P+1*32A/ IT output 5(4*40A+1*16A) 2*40A/1P+3*16A/1P 2P Smoke sensor, T & H sensor, Smoke sensor, T & H sensor, Standard intelligent lock, 10-inch PAD, intelligent lock, 10-inch PAD, Smoke sensor, T & H sensor, SMS/email alarm Configuration SMS/email alarm*, and local SMS/email alarm*, and local app O & M app O & M Fire extinguishing module, Fire extinguishing module, video surveillance, water Home A/C restart function, video surveillance, water video surveillance, water Optional leakage sensor, and mobile leakage sensor, door sensor, and mobile O & M”
Technical Deep Dive
The FusionModule500 integrates a single UPS whose available output capacity is either 6 kVA or 10 kVA (the two SKUs differ only in available rack space: the 6 kVA unit leaves up to 37U free and the 10 kVA unit up to 36U, with no battery pack installed). Huawei's current product specification lists 'Capacity: 6kVA/10kVA' under the power system section and does not offer a 3 kVA or a 15 kVA variant for this module, so only the 10 kVA and 6 kVA options are supported.
FusionModule500 uses 6 kVA and 10 kVA rack-mounted UPS capacities in its BC configurations. BC1L and BC3L use 6 kVA; BC2L uses 10 kVA; the specified Latin America BC4L uses 6 kV
A.
A 3 kVA or 15 kVA option is not listed. IT power limits still depend on cooling configuration and electrical design; nominal UPS kVA does not by itself define allowable cabinet heat load.
The FusionModule500 family contains cooled and noncooled configurations with different IT power limits. The selected UPS, room cooling conditions, battery runtime and enclosure arrangement must be checked together. A rating for a particular BC configuration must not be presented as the maximum or standard feature of every FusionModule500 installation.
Source reference: uploaded Huawei training material, PDF page 53.